D-Ex Instruments

Eaton

 Zenerovy bariéry - Volba bariéry podle aplikace


The MTL7700 Series, with their advanced features, should be regarded as your first choice for all new designs or installations. The recommendations below are based therefore on the MTL7700 Series.

Users of MTL700, 4700 or 7000 Series products can also use the guide because of MTL's consistent numbering policy. Products, in any barrier series, that have the same two last digits (ignoring letters and '+' symbols) will have very similar characteristics, e. g. MTL7787 and MTL787 or MTL7087.

Click for a table of alternatives to earlier barrier models

Analogue Inputs (high level)
  • 2-wire transmitters, 4-20 mA conventional and 'smart'
  • vibration probes
  • gas detectors
  • Analogue Inputs (low level)
  • thermocouples and mV sources
  • ac sensors, photocells, microphones & flowmeters
  • slidewire displacement transducers
  • 2, 3 and 4-wire RTDs
  • strain-gauge bridges - single
  • strain-gauge bridges - double
  • Analogue Outputs
  • controller outputs (I/P converters)
  • Digital (ON/OFF) Inputs
  • switches
  • proximity detectors/switches
  • Digital (ON/OFF) Outputs
  • alarms, LEDs, solenoid valves, etc.
  • Digital (ON/OFF) Input/Output
  • -ve/floating supply
  • AC/DC systems
  • 2-wire dc/ac systems and signal returns

  • Analogue Input - 2-wire transmitters, 4-20 mA conventional and 'smart'

    Power Supply Barrier
    Loops
    Voltage for Tx
    and lines
    Main features
    Regulated MTL7787+

    1

    12.4 V
    Compatible with most smart Tx's
    MTL7787P+ 1 13.1 V Higher power, IIC gases
    MTL7788R+ 1 13.7 V 1-5 V safe area ouput
    Unregulated
    20 to 35 V
    MTL7706+
    1
    15.5 V
    (250 ohm load)
    High accuracy; compatible with most smart transmitters; full output voltage
    available independently of supply voltage
    MTL7707P+ 1 13.0 V Higher power, IIB gases

    Analogue Input - vibration probes

    Power Supply Barrier
    Loops
    Main features
    Regulated MTL7796– 1 For –24 V systems

    Analogue Input - gas detectors

    Power Supply Barrier
    Loops
    Main features
    Nominal 6 V supplies MTL7758+ 1 For high current/low voltage
    MTL7758+ Vwkg = 6.0 V

    Analogue Input - thermocouple & mV sources

    Power Supply Barrier
    Loops
    Max end to enc
    resistance
    per loop
    Main features
    Earth-free signal, receiver
    input floating
    MTL7760ac 1 150 ohm
    Moving coil or low resistance receivers MTL7755ac 1 38 ohm

    Analogue Input - ac sensors, photocells, microphones & flowmeters

    Power Supply Barrier
    Loops
    Max end to enc
    resistance
    per loop
    Main features
    Earth-free signals up to a few kHz MTL7760ac 1 150 ohm

    Analogue Input - slidewire displacement transducers

    Power Supply Barrier
    Loops
    Vwkg Main features
    For nominal
    6 V supplies
    MTL7760ac 1 6.0 V

    Analogue Input - 2, 3 and 4-wire RTDs

    Power Supply Barrier
    Loops
    Main features
    2-wire MTL7755ac

    1

    2 channels track to 0.15 ohm
    3-wire MTL7755ac 2/3 End-to-end resistance 19 ohm/channel
    MTL7756ac 1 End-to-end resistance 19 ohm/channel
    4-wire MTL7755ac
    1/2
    Needs 2 barriers
    MTL7760ac 1/2 Vwkg = 6 V; needs 2 barriers
    MTL7761ac 1/2 Vwkg = 6 V; needs 2 barriers

    Analogue Input - strain-gauge bridges (single)

    Power Supply Barrier
    Loops
    Volts for 350 ohm bridge
    IIC gases MTL7761ac (2) +
    MTL7764ac (1)
    1 9.75 V from MTL7766Pac with 20 V supply

    Analogue Input - strain-gauge bridges (multiple)

    Power Supply Barrier
    Loops
    Volts for 350 ohm bridge (20 V in)
    Number of bridges
    1.............2..........3............4
    IIC gases MTL7761ac (2) +
    MTL7766ac (1)
    1 13.0..........9.2..........7.7.............6,2

    Analogue Output - controller outputs (I/P converters)

    Power Supply Barrier
    Loops
    Volt drop
    at 20 mA
    Main features
    Output goes to 0V (earth return); regulated supplies MTL7728+

    1

    6.8 V
    MTL7728P+ 1 5.1 V Higher power, IIC gases
    MTL7729P+ 1 3.7 V Higher power, IIB gases
    Transistor between controller output and 0V; (diode return); regulated supplies MTL7787+ 1 8.1 V
    MTL7787P+ 1 6.4 V Higher power, IIC gases
    Transistor between controller output and 0V; (diode return); unregulated supplies (20 to 35 V) MTL7707+
    1
    8.6 V
    MTL7707P 1 6.0 V Higher power, IIC gases

    Digital Input - switches

    Power Supply Barrier
    Loops
    Main features
    Regulated MTL7787+ 1 Diode return
    MTL7787P+ 1  
    MTL7789+ 2  

    Digital Input - switches / proximity detectors

    Power Supply Barrier
    Loops
    Main features
    Unregulated 22-35 V MTL7741 1 Changeover relay output
    MTL7742 1 Transistor output, fast switching
    MTL7743 2 2 x relay contacts
    MTL7744 2 2 x transistor output
    MTL7745 1 Single channel relay + LFD

    Digital Output - alarms, LEDs, solenoid valves, etc

    Power Supply Barrier
    Loops
    Usable power per loop Main features
    Switch in power leg, (earth return); regulated supplies MTL7728+

    1

    0.48 W
    MTL7728P+ 1 0.59 W Higher power, IIC gases
    Voltage drop = 5.1 V at 20 mA
    MTL7729P+ 1 0.82 W Higher power, IIB gases
    Control switch on earth (diode return); regulated supplies MTL7787+ 1 0.42 W
    MTL7787P+ 1 0.51 W Higher power, IIC gases
    Transistor between controller output and 0V; (diode return); unregulated supplies (20 to 35 V) MTL7707+
    1
    0.29 W Až 35 mA available
    MTL7707P+ 1 0.68 W Optimised for IIB gases

    Digital Input/Output - –ve and floating supplies

    Power Supply Barrier
    Loops
    Volts for 350 ohm bridge
    Regulated negative/floating
    power supply
    MTL7728– 1

    2-wire DC/AC systems - signal returns

    System or Function Barrier
    Loops
    Vwkg Main features
    6 V dc systems MTL7710+

    1

    6.0 V
    8 V dc system MTL7710P+ 1 8.0 V End ot end resistance 42 ohm.
    5 V at 65mA from 8 V supply. IIC gases
    Low-level logic returns MTL7764+ 2 10.0 V End-to-end resistance 1050 ohms
    12 V dc systems MTL7715+ 1 12.0 V
    MTL7715P+ 1 12.6 V
    18 V dc systems MTL7722+ 1 19.6 V
    2-wire dc/ac systems MTL7778ac 1 24.0 V
    Signal returns MTL7789+
    2
    26.6 V 2 diode return channels + power
    Securing cables to earth for future use; terminating cable screens MTL7799 Bussed power feed - not certified